Walk into any hardware store in the USA and you will see wire labelled 14 AWG, 12 AWG or 10 AWG. AWG stands for American Wire Gauge, the system used in North America to size electrical wire. The confusing part is that a bigger number means a smaller wire.
What Is AWG?
American Wire Gauge is a standard for wire diameter. A 14 AWG wire is thinner than a 12 AWG wire, and a 12 AWG wire is thinner than a 10 AWG wire. As the gauge number goes down, the wire gets thicker, its resistance goes down, and it can safely carry more current.
The chart below compares many wire sizes at a glance. Each circle is drawn to scale, and the chart lists the diameter in millimetres and the cross-sectional area in square millimetres for each size.
Diagram: A wire gauge comparison chart. Each circle is drawn to scale: a smaller AWG number means a larger wire. Find 14, 12 and 10 AWG in the chart.
Common Sizes and Their Ampacity
Ampacity is the maximum current a wire can carry without getting too hot. The main ampacity table in the NEC is Table 310.16, for copper conductors with not more than three current-carrying conductors in a raceway or cable at 30 degrees Celsius (86 degrees Fahrenheit).
Here are the common residential sizes, with copper ampacity from Table 310.16 (60 / 75 / 90 degrees C) and maximum breaker size:
14 AWG: 1.628 mm diameter, 2.08 square mm. Ampacity 15 / 20 / 25 A. Maximum breaker 15 A.
12 AWG: 2.053 mm diameter, 3.31 square mm. Ampacity 20 / 25 / 30 A. Maximum breaker 20 A.
10 AWG: 2.588 mm diameter, 5.26 square mm. Ampacity 30 / 35 / 40 A. Maximum breaker 30 A.
8 AWG copper: ampacity 40 / 50 / 55 A.
Notice that the breaker limit is lower than the ampacity in the 75 and 90 degree columns. That is because of NEC 240.4(D), the small-conductor rule, which caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper. Never put a 30-amp breaker on a 14 AWG circuit. Use the 75 degree column for most residential work, since most breakers are rated at 75 degrees C.
How to Choose a Wire Size in 4 Steps
Step 1: Find the load current in amps. For a continuous load, one that runs for 3 hours or more, size the conductor at 125 percent of the load current. Step 2: Pick the breaker size. A 15-amp circuit normally uses 14 AWG, a 20-amp circuit uses 12 AWG, and a 30-amp circuit uses 10 AWG.
Step 3: Check the length. On a long run, voltage drop can be a problem. Many designers aim for about 3 percent voltage drop or less. If the run is long, go one size larger. Step 4: Apply corrections. A hot attic or a conduit with more than three current-carrying conductors reduces the ampacity, so you may need a larger wire.
Difference Between Solid and Stranded Wire
Solid wire: a single copper conductor. It is cheap and is used in most fixed house wiring, such as NM-B cable. It holds its shape but is stiff and can break if bent back and forth many times.
Stranded wire: made of many fine copper strands twisted together. It bends easily, so it is used in flexible cords, control wiring and larger feeders, where the wire must move or be pulled around bends.
Diagram: A stranded copper wire. Stranded wire is flexible and easy to pull, while solid wire is common in fixed house wiring.
Difference Between Copper and Aluminium Wire
Copper: the standard choice. It carries more current for the same size, makes reliable connections, and is used for almost all branch circuits in homes. For example, 12 AWG copper gives 20 A at 60 degrees C and 25 A at 75 degrees C.
Aluminium: lighter and cheaper, but it needs a larger size for the same current: 12 AWG aluminium has an ampacity of only 15 A at 60 degrees C and 20 A at 75 degrees C. It is used mainly for larger service feeders, and its connections need special care because aluminium expands more with heat and oxidises at the surface.
Key Takeaways
In the AWG system, a smaller number means a bigger wire. Learn the three everyday sizes by heart: 14 AWG for 15-amp circuits, 12 AWG for 20-amp circuits and 10 AWG for 30-amp circuits. Always check NEC Table 310.16 for ampacity, respect the breaker caps in NEC 240.4(D), and size continuous loads at 125 percent.
Objective Questions
1. In the AWG system, what does a bigger gauge number mean?
a) A thicker wire
b) A smaller, thinner wire
c) A longer wire
d) A higher voltage rating
Answer: (b) A smaller, thinner wire
Explanation: In AWG the numbers work backwards: a 14 AWG wire is thinner than a 12 AWG wire, and a 12 AWG wire is thinner than a 10 AWG wire.
2. Which NEC table gives the ampacity of copper and aluminium conductors?
a) Table 210.52
b) Table 240.4
c) Table 310.16
d) Table 430.52
Answer: (c) Table 310.16
Explanation: NEC Table 310.16 is the main ampacity table, for conductors with not more than three current-carrying conductors in a raceway or cable at 30 degrees C (86 degrees F).
3. From NEC Table 310.16, what is the ampacity of 12 AWG copper at 75 degrees C?
a) 20 A
b) 25 A
c) 30 A
d) 35 A
Answer: (b) 25 A
Explanation: Table 310.16 gives 12 AWG copper an ampacity of 20 A at 60 degrees C, 25 A at 75 degrees C and 30 A at 90 degrees C.
4. Which NEC rule caps the breaker size for small conductors, so that 14 AWG copper can have at most a 15 A breaker?
a) NEC 210.8
b) NEC 240.4(D)
c) NEC 250.52
d) NEC 310.16
Answer: (b) NEC 240.4(D)
Explanation: NEC 240.4(D), the small-conductor rule, caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG copper.
5. A load runs for 3 hours or more. What is it called, and at what percentage of its current must the conductor be sized?
a) Intermittent load, 100 percent
b) Continuous load, 125 percent
c) Non-continuous load, 80 percent
d) Peak load, 150 percent
Answer: (b) Continuous load, 125 percent
Explanation: A load that runs for 3 hours or more is a continuous load, and the conductor must be sized at 125 percent of the load current.